How long a solar battery bank keeps a load running once the sun has gone. Three things end the night before the bank is actually empty: the depth of discharge the chemistry tolerates, the inverter's low-voltage cutoff, and on lead-acid the Peukert effect, which shrinks the bank the harder you pull on it. This tool models the first and third by chemistry and explains the second, so the answer for a 200 Ah flooded bank on a 12 V van and a 200 Ah lithium bank on a 48 V house are as different as they are in practice.
Sets the Peukert exponent and the default depth of discharge.
Free download
DC cable ampacity with the ambient and bundling corrections, how far each size runs at 12, 24 and 48 V, PV string fuse sizes from Isc, and battery-to-inverter current by inverter size. Three pages, made to pin by the battery bank.
The first pass treats the bank as a tank:
That is right for lithium and optimistic for lead-acid. A lead-acid Ah rating is quoted at the 20-hour rate, C/20, and the faster you empty it the less you get out. Peukert's law puts a number on that. The tool computes the discharge current at the battery, I = Load ÷ (V × efficiency), and then:
with k = 1.25 for flooded cells, 1.15 for AGM and gel, and 1.02 for LFP, which is close enough to linear to be a formality. At exactly the C/20 rate the bracket is 1 and the two answers agree; the correction is under 3% down to about C/20 and past 15% beyond C/8, which is where the tool starts flagging it.
Every inverter has a low-voltage disconnect, and the inverter sizing calculator defaults it to 87.5% of nominal: 10.5 V on a 12 V bank, 21 V at 24 V, 42 V at 48 V. Under a heavy load the terminal voltage of a lead-acid bank sags well below its resting voltage, so the inverter can trip on the cutoff with charge still in the cells, then the voltage recovers and it looks like a fault. Lithium holds its voltage almost flat until the end and then falls off a cliff, so on LFP the DoD limit is what you hit; on lead-acid under load it is often the cutoff. Either way, a runtime that ends at the cutoff is shorter than the one above.
200 Ah lithium LFP at 48 V, 0.8 DoD, 92% efficiency, carrying a steady 500 W:
200 Ah flooded lead-acid at 12 V, 0.5 DoD, 92% efficiency, the same 500 W:
Same number on the label, 14 hours against an hour and a half. The voltage accounts for a factor of four, the depth of discharge for another 1.6, and the discharge rate for the rest. Drop the load on that flooded bank to 100 W and the current falls to 9.1 A, C/22, slower than the rating condition, and the Peukert term stops mattering: 11.0 hours linear and the tool shows no correction.
An off-grid bank is sized the other way round: how many days of no useful sun it has to cover, not how many hours one load runs. Daily kWh times days of autonomy, divided by DoD, round-trip efficiency and the cold-weather derate, then divided by the bank voltage for the amp-hours. The battery bank size calculator does that and turns the answer into a count of real batteries; the off-grid load calculator produces the daily kWh it starts from. Because a bank sized on autonomy always discharges slowly on average, Peukert costs you on the peak loads, the kettle and the microwave, not on the average, which is why this tool takes a single load rather than a daily total.
| Chemistry | Default DoD | Peukert k | Round-trip efficiency | What usually ends the runtime |
|---|---|---|---|---|
| Lithium LFP | 0.8 | 1.02 | 0.95 | The BMS or the DoD you set; voltage stays flat until then |
| AGM | 0.5 | 1.15 | 0.85 | The inverter cutoff under a heavy load |
| Gel | 0.5 | 1.15 | 0.85 | As AGM, and gel dislikes high currents more |
| Flooded lead-acid | 0.5 | 1.25 | 0.80 | Peukert past C/8, then the cutoff |
Round-trip efficiency is what the battery bank size calculator applies when it sizes the bank for recharging; this tool's efficiency field is the discharge-side loss through the inverter and wiring, which is why it defaults to 0.92 for every chemistry. Setting a lead-acid DoD above 0.5 is allowed, and flagged, because it costs cycle life.
It depends far more on the voltage and the chemistry than on the 200 Ah. At 48 V on lithium LFP with 0.8 depth of discharge and 92% efficiency, about 14.1 hours. At 12 V on flooded lead-acid at 0.5 DoD, 2.2 hours by the linear sum and about 1.5 hours once Peukert's effect is applied, because 500 W from 12 V is a 45 A, C/4.4 discharge. Enter your own bank above; the chemistry selector sets both the DoD default and the Peukert exponent.
0.5 for flooded, AGM and gel, and 0.8 for lithium iron phosphate; those are the defaults the tool applies when you change chemistry. Lead-acid cycle life falls steeply below half charge, so the tool flags any lead-acid DoD above 0.5 rather than refusing it. LFP tolerates 0.8 routinely and some makers rate it to 0.9 or more; use the figure from your battery's own cycle-life curve.
The low-voltage cutoff. Inverters disconnect at a set terminal voltage, typically 10.5 V on a 12 V bank, 21 V at 24 V and 42 V at 48 V, and a lead-acid bank under a heavy load sags below that long before its depth-of-discharge limit. The voltage recovers once the load drops, which is why it reads as charge left. Lithium holds a flat voltage until the end, so on LFP the cutoff rarely fires early; on lead-acid it is usually what actually ends the runtime.
A lead-acid battery's Ah rating is measured over 20 hours, and discharging it faster delivers fewer amp-hours. The tool applies runtime = 20 × (C ÷ (I × 20))k × DoD with k = 1.25 for flooded, 1.15 for AGM and gel and 1.02 for LFP. Below the C/20 rate the correction is negligible and the tool hides it; between C/20 and C/8 it grows to a few percent; past C/8 it exceeds 15% and the tool flags it. On a 12 V bank almost any inverter load is past C/8, which is the practical case for lithium in a van.
Because amp-hours are not energy. Watt-hours are amp-hours times voltage, so 200 Ah holds 2,400 Wh at 12 V and 9,600 Wh at 48 V. A 48 V house bank and a 12 V van bank with the same Ah label are not remotely comparable, and comparing banks by Ah across voltages is the commonest way a runtime estimate ends up wrong by a factor of two or four. Compare in Wh, which is what this tool reports alongside the hours.
Continue with these related solar tools
Battery bank capacity in Ah and kWh from daily use, days of autonomy, depth of discharge and temperature
Add up every appliance to get daily watt-hours, amp-hours and the peak load your inverter has to carry
Continuous and surge inverter rating from your load, plus the DC input current the battery cable has to carry
Add this free calculator to your website. Copy the code below and paste it into your page.
Free solar and off-grid sizing calculators
© 2026 Solar Sizing Calculator. All rights reserved. A Nomogram Works site.